(495) 544 66 75
         
 

MGF Comparison

MGF Comparative characteristics to main import filtering mediums in equal status exploitation


№ п/п Characteristics,
Service conditions
BIRM MGF MZ Greensand QUANTUM
DMI-65
1. Raw materials Silicon dioxide, coated manganese dioxide Dolomite Zeolite potassium permanganate Catalist sand
2. Maximum manganese allowance (Mn) and iron (Fe) in purifying water 4 Up to 50 15 20
3. Water oil products and oil admissibility no Acceptable Acceptable Acceptable
4. H2S admissibility in water no Acceptable Acceptable Acceptable
5. Sensitivity to chlorine in purifying water Violent activity contraction no no Violent activity contraction
6. Oxidant used by filtering mediums   oxygen Any KMnO4 Continued dosing by hypochlorite sodium
7. pH value operative range 7,0 - 9,0 4,5 - 9,0 6,8 - 8,8 5,8 - 8,6
8. Need for correction pH values рН <6,8 No necessity рН <6,2 рН <6,2
9. Capacitance by Fe (g Fe on dm3 fill) 1,0 2 0,5 - 0,64 0,5
10. Regeneration cycle structure, regeneration algorithm Water backwashing Water backwashing; approximate time – 15 minutes Backwashing, regeneration (fill characteristics reclaiming by means KMnO4) post-regeneration cleaning; 1,5-2 hours Backwashing; approximate time – 15 minutes